AC test power supply

video
product name

WF series non-partial discharge power supply

Model:

Power:

Energy:

Description: Product overview:The W-F series partial discharge-free power supply utilizes an excitation transformer to activate either series or parallel resonant circuits. By adjusting the output frequency of the power supply, it induces resonance between the reactor's inductance and the specimen's capa

Products Description

Product overview:

The W-F series partial discharge-free power supply utilizes an excitation transformer to activate either series or parallel resonant circuits. By adjusting the output frequency of the power supply, it induces resonance between the reactor's inductance and the specimen's capacitance within the circuit, generating a resonant voltage equivalent to the applied voltage on the specimen. Alternatively, the intermediate transformer can directly output the voltage to the primary side for induction withstand voltage testing. This system is applicable for AC withstand voltage testing and partial discharge testing of all electrical equipment.


Product features:

● Output waveform is good, low voltage harmonic distortion rate, low harmonic content;

● Strong overload capacity, power unit modularization, can withstand the impact current of the motor, and does not cause voltage drop;

● Fast dynamic response, sudden load voltage transient change is small, fast recovery time;

● Intuitive display, easy to operate, using LCD Chinese and English touch operation display;

● Excellent stability, high frequency stability, produced by quartz oscillator, very stable and accurate frequency;

● Strong anti-interference, using optical fiber drive control, has strong anti-electromagnetic interference and reliability;

● High protection level, the surface of the equipment cabinet is treated with electrostatic spraying, and the PCB is treated with three-proof spray paint and potting compound.


App industries:

It is used for AC withstand voltage and partial discharge test in fields such as transformers, circuit breakers, switches, GIS systems, cables, bushings, insulated terminals, etc.

 

 unit type

WF60

-31100

WF60

-31150

WF60

-31200

WF60

-31300

WF60

-31450

 power rating

10KVA

15KVA

20kVA

30KVA

45KVA

Input exchange indicators

Power supply type

Three phase four wire +PE

 voltage range

380V(±15W)

 frequency range

50/60Hz(±10W)

Output AC characteristics

Power supply type

Single phase two wire

 voltage range

0~800V- (standard)/0~1000V- (optional)

 current range

12A

18A

25A

37A

60A

 frequency range

Fixed frequency: 50/60Hz, frequency modulation: 30~300Hz

Source effect

0.1MFS

Load effect

0.1%F.S

 voltage accuracy

0.1%F.S

Frequency accuracy

0.01%F,S

Voltage harmonics

2W

 response time

5ms

Volume increases

20pC (standard)/10pC (optional)/5pC (optional)

 device efficiency

90%

 overload capacity

120%~150%,1min; 150W~200%,2s; 200%. Immediately shut off output

 system function

Online adjustment function

The output voltage and frequency can be adjusted online

Quick Settings feature

Multiple sets of output voltage and frequency can be customized

 memory function

After power failure recovery, the last output mode and parameters can be remembered

 defencive function

Input undervoltage and phase loss protection, output overvoltage, overcurrent, overload, short circuit protection, internal overheating protection, etc

Display and communications

Local operation

LCD display screen

 display resolution

Voltage: 0.1V, current: 0.1A, frequency: 0.1Hz, power: 0.1kW

Display accuracy

Voltage: 0.1MFS, current: 0.2%F.S, frequency: 0.01%, power: 0.3F.S

 telecommunication

RS 485/LAN

 protocol

Standard Modbus RTU/Modbus TCP/IP

Safety performance

 compression strength

2000Vdc/60s/ no breakdown

 insulation resistance

20MΩ@500Vdc

 earthing resistance

100mΩ

 noise

65dB(A)

 service environment

 work environment

The ambient temperature is-20~45, and the relative humidity is 0~95%, which can work continuously for 24 hours

 cooling-down method

Fan forced air cooling

 levels of protection

IP 21

 above sea level

No more than 5000m@>2000m reduced use

Power supply (W*D+H) mm

400*560*800

(including mobile wheels)

400*660*800

(including mobile wheels)

500×8201100

(including mobile wheels)

500*820+1100

(including mobile wheels)

520*1160*1355

(including mobile wheels)

 filter WD+Hmm

600*400*162

600*400*162

600400*162

600-400+162

1000+572*162


 

 unit type

WF60

-31600

WF60

-311000

WF60

-312000

WF60

-313000

WF60

-314000

 power rating

60KVA

100KVA

200kKVA

300kVA

400KVA

Input exchange indicators

Power supply type

Three phase four wire +PE

 voltage range

380V(±15M)

 frequency range

50/60Hz(±10%)

Output AC characteristics

Power supply type

Single phase two wire

 voltage range

0~800V- (standard)/0~1000V- (optional)

 current range

75A

125A

250A

375A               500A               375A               500A

 frequency range

Fixed frequency: 50/60Hz, frequency modulation: 30~300Hz

Source effect

0.1%F.S

Load effect

0.1%F.S

 voltage accuracy

0.1%F.S

Frequency accuracy

0.01%F.S

Voltage harmonics

2%

 response time

5ms

Volume increases

20pC (standard)/10pC (optional)/5pC (optional)

 device efficiency

90%

 overload capacity

120%~150%,1min; 150W~200%,2s; 200%, immediately shut off output

 system function

Online adjustment function

The output voltage and frequency can be adjusted online

Quick Settings feature

Multiple sets of output voltage and frequency can be customized

 memory function

After power failure recovery, the last output mode and parameters can be remembered

 defencive function

Input undervoltage, phase loss protection, output overvoltage, overcurrent, overload, short circuit protection, internal overheating protection, etc

Display and communications

Local operation

LCD display screen

 display resolution

Voltage: 0.1V, current: 0.1A, frequency: 0.1Hz, power: 0.1kW

Display accuracy

Voltage: 0.1%F.S, current: 0.2MFS, frequency: 0.01%, power: 0.3%F.S

 telecommunication

RS 485/LAN

 protocol

Standard Modbus RTU/Modbus TCP/IP

Safety performance


 compression strength

2000Vdc/60s/ no breakdown

 insulation resistance

20MΩ@500Vdc

 earthing resistance

100mΩ

 noise

65dB(A)

 service environment

 work environment

The ambient temperature is-20~45, and the relative humidity is 0~95%, which can work continuously for 24 hours

 cooling-down method

Fan forced air cooling

 levels of protection

IP 21

 above sea level

No more than 5000m@>2000m reduced use

Power supply (W*D+H) mm

520*1160+1355

(including mobile wheels)

650*1420*1470

(including mobile wheels)

1910*1160*1940

1910*1160*1940

1910*1160*1940

 filter WAD*Hmm

1000*572*162

1000*572*162

1300*700*260

1300*700*260

1300*700*260

 


 unit type

WF60

-33100

WF60

-33200

WF60

-33300

WF60

-33450

WF60

-33600

WF60

-33900

 power rating

10KVA

20KVA

30kVA

45KVA

60KVA

90kVA

Input exchange indicators

Power supply type

Three phase four wire +PE

 voltage range

380V(±15%)

 frequency range

50/60Hz(±10W)

Output AC characteristics

Power supply type

Three phase four wire

 voltage range

0~800V- "standard") /0~1000V (optional)

 current range

7A

14A

21A

32A

42A

63A

 frequency range

Fixed frequency: 50/60Hz, frequency modulation: 30~300Hz

Source effect

0.1%F.S

Load effect

0.1%F.S

 voltage accuracy

0.1%F.S

Frequency accuracy

0.01%F.S

Voltage harmonics

2W

 response time

5ms

Volume increases

20pC (standard)/10pC (optional)/5pC (optional)

 device efficiency

90%

 overload capacity

120%~150%,1min; 150%~200%,2s; 200%, immediately shut off output

 system function

Online adjustment function

The output voltage and frequency can be adjusted online

Quick Settings feature

Multiple sets of output voltage and frequency can be customized

 memory function

After power failure recovery, the last output mode and parameters can be remembered

 defencive function

Input undervoltage, phase loss protection, output overvoltage, overcurrent, overload, short circuit protection, internal overheating protection, etc

Display and communications

Local operation

LCD display screen

 display resolution

Voltage: 0.1V, current: 0.1A, frequency: 0.1Hz, power: 0.1kW

Display accuracy

Voltage: 0.1%F.S, current: 0.2%F.S, frequency: 0.01%, power: 0.3%F.S

 telecommunication

RS 485/LAN

 protocol

Standard Modbus RTU/Modbus TCP/IP

Safety performance


 compression strength

2000Vdc/60s/ no breakdown

 insulation resistance

20MΩ@500Vdc

 earthing resistance

100mΩ

 noise

65dB(A)

 service environment

 work environment

The ambient temperature is-20~45, and the relative humidity is 0~95%, which can work 24 hours continuously

 cooling-down method

Fan forced air cooling

 levels of protection

IP 21

 above sea level

No more than 5000m@>2000m reduced use

Power supply (W*D*H) mm

500*820*1100

(including mobile wheels)

500*820*1100

(including mobile wheels)

520+1160*1355

(including mobile wheels)

520*1160*1355

(including mobile wheels)

650+1420*1470

(including mobile wheels)

650*1420+1470

(including mobile wheels)

 filter W+D+Hmm

800*500*162

800*500*162

800+500*162

800*500*162

1000*600*162

100D*600*162

 

 unit type

WF60

-331000

WF60

-331200

WF60

-331500

WF60

-332000

WF60

-333000

WF60

-334000

 power rating

100KVA

120KVA

150KVA

200KVA

300KVA

400kVA

Input exchange indicators


Power supply type

Three phase four wire +PE

 voltage range

380V(±15%)

 frequency range

50/60Hz(±10%)

Output AC characteristics

Power supply type

Three phase four wire

 voltage range

0~800V (standard) /0~1000V (optional)

 current range

72A

86A

108A

144A

216A

288A

 frequency range

Fixed frequency: 50/60Hz, frequency modulation: 30~300Hz

Source effect

0.1%F.S

Load effect

0.19%F.S

 voltage accuracy

0.1%F.S

Frequency accuracy

0.01%F,S

Voltage harmonics

2%

 response time

5ms

Volume increases

20pC (standard)/10pC (optional)/5pC (optional)

 device efficiency

90%

 overload capacity

120%~150%,1min; 150W~200%,2s; 200%, immediately shut off output

 system function

Online adjustment function

The output voltage and frequency can be adjusted online

Quick Settings feature

Multiple sets of output voltage and frequency can be customized

 memory function

After power failure recovery, the last output mode and parameters can be remembered

 defencive function

Input undervoltage, phase loss protection. Output overvoltage, overcurrent, overload, short circuit protection, internal overheating protection, etc

Display and communications

Local operation

LCD display screen

 display resolution

Voltage: 0.1V, current: 0.1A, frequency: 0.1Hz, power: 0.1kW

Display accuracy

Voltage: 0.1%F.S, current: 0.2MFS, frequency: 0.01%. Power: 0.3%F.S

 telecommunication

RS 485/LAN

 protocol

Standard Modbus RTU/Modbus TCP/IP

Safety performance


 compression strength

2000Vdc/60s/ no breakdown

 insulation resistance

20MΩ@500Vdc

 earthing resistance

100mQ

 noise

65dB(A)

 service environment

 work environment

The ambient temperature is-20~45, and the relative humidity is 0~95%, which can work continuously for 24 hours

 cooling-down method

Fan forced air cooling

 levels of protection

IP 21

 above sea level

No more than 5000m@>2000m reduced use

Power supply (W-DH) mm

650*1420*1470

(including mobile wheels)

650*1420+1470

(including mobile wheels)

650*1420*1470

(including mobile wheels)

1550*8501985

(including mobile wheels)

1550*850*1985

(including mobile wheels)

1910*1160*1940

 filter W*DHmm

1000*600*162

1000+600×162

1000*600×162

1300*770*260

1300*770*260

1300*770-260

 